Loading
BASELAYER EDGE is designed for both indoor and outdoor deployments.
BASELAYER EDGE XA10
EDGE XA10 HPC Data Module
Outdoor or Indoor Deployable Data Module that delivers up to 600 kW of Critical IT power and Economized Cooling for up to twenty (20) 52U Cabinets @ N • Engineered to meet NEMA 4 compliance standards for deployment in all global environmentsUnit PUE Range
As low as 1.05
(Dependent upon Environmental and Operational Conditions)
Maximum Module Capacity
Maximum Available kW at 25 °F ΔT
@N
600 kW
@N+1
500 kW
@2N
300 kW
Maximum Module Density, kW/Cabinet
(20) 24″ (609 mm) Cabinets
(16) 30″ (762 mm) Cabinets
@N
30 kW/Cabinet
37.5 kW/Cabinet
@N+1
25 kW/Cabinet
31.2 kW/Cabinet
@2N
15.0 kW/Cabinet
18.7 kW/Cabinet
Security
Access Control
Open Compartmentalized Architecture, Enhanced Security Encryption, Versatile Interoperability, Proximity Card Readers (Keypad and Biometric Options Available), Layers of Physical & Logical Protection, Separate IT & Support Space Access
Cameras
Pre-wired for IP Based Cameras
Door Locks
Electronic Locks
Fire System
Dedicated Fire System
Externally Accessible Fire Control Panel, Pre-Discharge Alarm & Strobe Lights, Fire Pull Station, Abort Hold Button and Keyed Bottle Disconnects
Smoke Detection
Aspirating Smoke Detection
Fire Suppression
Clean Agent Fire suppression (Non-Ozone Depleting Agent)
Fire Rating
NFPA 72 Compliant and UL-Listed Fire Equipment
Exterior Dimensions
US(Metric)
Length
Width
Height
42’ 8” (13.0 m)
23′ 0″ (7.0 m)
13’ 3” (4.0 m)
IT Space Dimensions
US(Metric)
Length
Width
Height
41’ 8” (12.7 m)
10’ 6” (3.2 m)
9’ 4” (2.8 m)
IT Space Area (Usable)
437 ft2 (42.5 m2)
US (Metric)
Technology-agnostic design with 437 ft2 of IT space.
Cold Aisle = 56″ (1.4 m), Hot Aisle = 36″ (.91 m)
Estimated Module
76,000 lbs. (34,473 kg) (Includes IT and Cooling Block)
Shipping Weight
US (Metric)
(Excludes IT Cabinets and Equipment)
Standard IT Cabinets
(20) 24” (609 mm) Cabinets (Up to 52U)
(Quantity)
(16) 30” (762 mm) Cabinets (Up to 52U)
Voltage/Frequency
400 V, 3-Phase, 50 Hz
480 V, 3-Phase, 60 Hz
Power Distribution (IT)
400 A Busway (Each Busway A and B), 800 A Optional
Cooling Type
Outside Air (OSA) Economizer with Chilled Water Trim, Counterflow Chilled Water Coils
and High Efficiency Plug Fans with Electronically Commutated Motors (ECM)
Leak Detection
Strip Leak Detection