BASELAYER CORE PC10


CORE PC10 Power Module

Power module is the first to receive UL 2755 safety listing for modular UPS installation Ships configuration tested from the factory with RunSmart Embedded providing access to key module sensors and controls via a web-based server Eliminate service interruption for routine maintenance and component upgrades Visualize power utilization; optimize redundancy and quality of service based on application needs Engineered for lower power loss across a wide load range without sacrificing performance or reliability UPS can be configured to operate independently or as part of a single system; chilled water economization capable

Download PC10 Spec Sheet
Unit PUE Range
As low as 1.15 (Dependent upon Environmental and Operational Conditions)

Module Power Delivery
2 x High Effiency Uninterruptible Power Supply (UPS) provides conditioned Uninterruptible A/C power
Critical IT Capacity (kVA)
@ N
1500 kVA
@ N+1
650 kVA
@ 2N
650 kVA
Ride Through (Load Specific)
5 minutes at 100% Load
Power Factor
1.0PF

Access Control
 
Compartmentalized Architecture, Role Based Access Control, Layers of Physical/Logical Protection, Separate Tech/Support Space Access

Fire System
Dedicated Fire System
Externally Accessible Fire Control Panel High Sensitivity Smoke Detection (HSSD) Pre-Discharge Alarm & Strobe Light
Fire Rating
3 Hour Doors
Download PC10 Spec Sheet
Exterior
Dimensions
US(Metric)
Length
Width
Height
42’ 8” (13.00m)
11’ 8” (3.55m)
13’ 5” (3.96m)

Interior Tech
Space Dimensions
US(Metric)
Length
Width
Height
42’ 0” (12.8m)
11’ 0” (3.35m)
8’ 4” (2.54m)

Estimated Module
Shipping Weight
US(Metric)
76,000 – 78,000 Lbs (34,473 – 35,380 kg)

Input Power
Voltage
480V, 3 Phase, 3Wire
Frequency
60Hz

Chilled Water Header
Bi-Directional, Supply/Return;Connections At Both Ends

Air Handling Units
4 x Modular 56kW AHU (standard wtih 4, upgradable to 8)

Leak Detection
Spot Leak Detection (9 total)

Make-Up Air Unit
1 x High Efficiency MAU
Download PC10 Spec Sheet
core frontcore front
core frontcore front
core frontcore front

DEPLOYMENT SCENARIO


BASELAYER CORE units are configurable in many deployment scenarios. This deployment delivers up to 1.2MW of Critical IT power and Cooling for up to fifty-four (54) 50U racks @ N redundancy.

BASELAYER deployments can consist of both power and data (IT) modules configured and tested from the factory with an enhanced integrated Module Control Unit (MCU) providing access to real-time module sensors.

Power and cooling redundancy thresholds, along with analytics and historic trending, are all available through BASELAYER® RunSmart OS

deployment module
SPECIFICATIONS & PERFORMANCE
Unit PUE Range
As low as 1.15
(Dependent upon Environmental and Operational Conditions)

Total Product Installation Footprint
3,207 ft2 (298.1m2)

Critical IT Footprint
1,386 ft2 (128.8m2)

Minimum Facility Ceiling Height
19’4″ ft (5.89m)

Access Control
Compartmentalized Architecture

Intelligent Control Interfaces
Customizable: Role Based Visibility, Warnings, Alarms, Thresholds & Control Set Points; BASELAYER RunSmart OS Integrates Both Modular and Legacy Data Center Infrastructure with IT Equipment

Dedicated Fire System
Each unit comes with an Externally Accessible Fire Control Panel and High Sensitivity Smoke

Available (UI) User Interface
Visualizer – Desktop and Mobile, Business Reporting, API Provide Real-time Visibility, Control, Optimization, and Automation

CE
Compliant
UL
UL 2755 Compliant
Uptime Institute
Product based on Tier III Design parameters
NFPA
Compliant