BASELAYER EDGE is designed for both indoor and outdoor deployments.
BASELAYER EDGE XC50
EDGE XC50 Modular Data Center
Outdoor or Indoor Deployable Modular Data Center that delivers up to 600 kW of Critical IT power and Cooling for up to one hundred ten (110) 52U Cabinets @ N • Engineered to meet NEMA 4 compliance standards for deployment in all global environmentsUnit PUE Range
As low as 1.15
(Dependent upon Environmental and Operational Conditions)
Maximum Module Capacity
Maximum Available kW at 25 °F ΔT
@N
600 kW
@N+1
500 kW
@2N
300 kW
Maximum Module Density, kW/Cabinet
(110) 24″ (609 mm) Cabinets
@N
5.4 kW/Cabinet
@N+1
4.5 kW/Cabinet
@2N
2.7 kW/Cabinet
Security
Access Control
Open Compartmentalized Architecture, Enhanced Security Encryption, Versatile Interoperability, Proximity Card Readers (Keypad and Biometric Options Available), Layers of Physical & Logical Protection, Separate IT & Support Space Access
Cameras
Pre-wired for IP Based Cameras
Door Locks
Electronic Locks
Fire System
Dedicated Fire System
Externally Accessible Fire Control Panel, Pre-Discharge Alarm & Strobe Lights, Fire Pull Station, Abort Hold Button and Keyed Bottle Disconnects
Fire Suppression
Clean Agent Fire suppression (Non-Ozone Depleting Agent)
Smoke Detection
Aspirating Smoke Detection
Fire Rating
NFPA 72 Compliant and UL-Listed Fire Equipment
Exterior
Dimensions
US(Metric)
Length
Width
Height
42’ 8” (13.0 m)
60’ 10” (18.5 m)
13’ 3” (4.0 m)
Interior Space Dimensions
US(Metric)
Length
Width
Height
41’ 8” (12.7 m)
52’ 6” (16.1 m)
9’ 4” (2.8 m)
IT Space Area (Usable)
1958 ft2 (182 m2)
US (Metric)
Technology-agnostic design with 1958 ft2 of IT space
Cold Aisle = 52″ (1.3 m), Hot Aisle = 36″ (.91 m) (Standard Configuration)
Estimated Module
152,000 lbs. (68,946 kg) (Includes IT and Cooling Blocks)
Shipping Weight
US (Metric)
(Excludes IT Cabinets and Equipment)
Number of Standard Cabinets
(110) 24” (609 mm) Cabinets (Up to 52U)
Voltage/Frequency
400 V, 3-Phase, 50 Hz
480 V, 3-Phase, 60 Hz
Power Distribution (IT)
400 A Busways Standard; Up to 800 A per Busway (Optional)
Cooling Type
Chilled Water, Counterflow Chilled Water Coils and High Efficiency Plug Fans with Electronically Commutated Motors (ECM)
Leak Detection
Strip Leak Detection