BASELAYER EDGE XP10


EDGE XP10 Power Block
The EDGE XP10 Power Block is a state-of-the-art switchboard and UPS featuring modularized critical components and delivers a configurable conditioned power supply.
Unit PUE Range
As low as 1.15
(Dependent upon Environmental and Operational Conditions)

Module Power Delivery
(2) High Efficiency Uninterruptible Power Supplies (UPS) provides conditioned Uninterruptible AC power

Critical IT Capacity
Maximum Available kW
@N
1500 kVA (Two UPSs at 750 kVA each)
@N+1
750 kVA
@2N
750 kVA

Ride Through (Load Specific)
5 minutes at 100%

Security
Access Control
Open Compartmentalized Architecture, Enhanced Security Encryption, Versatile Interoperability, Proximity Card Readers (Keypad and Biometric Options Available), Layers of Physical & Logical Protection
Cameras
Pre-wired for IP Based Cameras
Door Locks
Electronic Locks

Fire System
Dedicated Fire System
Externally Accessible Fire Control Panel, Pre-Discharge Alarm & Strobe Lights, Fire Pull Station, Abort Hold Button and Keyed Bottle Disconnects
Fire Suppression
Clean Agent Fire suppression (Non-Ozone Depleting Agent)
Smoke Detection
Aspirating Smoke Detection
Fire Rating
NFPA 72 Compliant and UL-Listed Fire Equipment
Exterior Dimensions US(Metric)
Length Width Height
42’ 8” (13.0 m) 11’ 8” (3.5 m) 13’ 5” (4.0 m)

Interior Tech Space Dimensions US(Metric)
Length Width Height
42′ 0″ (12.8 m) 11’ 0” (3.3 m) 8’ 5-1/2” (2.6 m)

Estimated Module Shipping Weight US(Metric)
78,000 Lbs (35.380 kg) (Excludes Storage Batteries)

Input Power
480V, 3 Phase, 60Hz
Voltage/Frequency
400V, 3 Phase, 50Hz

UPS Type
Online, Double-Conversion, Transformer Free, Insulated-Gate Bipolar Transistor (IGBT) with Pulse-Width Modulation

UPS Energy Storage
VRLA Battery Strings, Lithium Ion (Optional)

Cooling Type
(2) 50 kW Chilled Water, (CRAH) Computer Room Air Handling Units (Standard); DX, (CRAC) Computer Room Air Conditioning Units (Optional)
Leak Detection
Spot Leak Detection
outdoor data center- edge front
outdoor data center- edge front
outdoor data center- edge front

DEPLOYMENT SCENARIO


BASELAYER EDGE units are configurable in many deployment scenarios. This deployment delivers up to 2.0 MW of Critical IT power and Cooling for up to eighty (80) 52U racks @ N redundancy.

BASELAYER deployments can consist of both power and data (IT) modules configured and tested from the factory with an enhanced integrated Module Control Unit (MCU) providing access to real-time module sensors. Engineered to meet NEMA 4 compliance standards for deployment in all global environments. Power and cooling redundancy thresholds, along with analytics and historic trending, are all available through BASELAYER RunSmart OS outdoor data center deployment module
SPECIFICATIONS & PERFORMANCE
Unit PUE Range
As low as 1.15
(Dependent upon Environmental and Operational Conditions)

Total Product Installation Footprint
8,451 ft2 (785.5m2)

Critical IT Footprint
1,833 ft2 (170.4m2)

Access Control
Compartmentalized Architecture

Intelligent Control Interfaces
Customizable: Role Based Visibility, Warnings, Alarms, Thresholds & Control Set Points; BASELAYER RunSmart OS Integrates Both Modular and Legacy Data Center Infrastructure with IT Equipment

Dedicated Fire
Dedicated 4-wire loop to signaling devices and initiating devices, with all batteries, amplifiers, transponders provided for a fully addressable fire alarm system. Pre-Discharge Alarm & Strobe Light

Available (UI) User Interface
Visualizer – Desktop and Mobile, Business Reporting, API Provide Real-time Visibility, Control, Optimization, and Automation

CE
Compliant
Outdoor Compliance
NEMA 4
UL
UL 2755 Compliant
NFPA
Compliant